14.3

Transmission Line - Digital Networks

Digital Interface DLE
Data rate
Path protection (1+1)
Internet Line Interface (EN100 - TPoP) *
ETH electrical
ETH optical
Path protection (1+1)
* Ethernet Line Interface (TPoP) is not applicable for integration into PLC system PowerLink or in combination
with IEC61850 command interface.
Transmission Time*
64 Kbps
2 Mbps
* Values are given for the IFC-P module.
If the IFC-D module is used, all specified signal transmission times are prolonged by about ≤ 4 ms.
With fiber-optic connections the transmission times are prolonged by about ≤ 1 ms.
If the EN100 module is used as GOOSE interface, the transmission times are prolonged by about ≤ 1 ms.
Security and Dependability
Security
Dependability
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
64 Kbps
2 Mbps
Digital and digital line
Digital and FO line
Digital and analog line
Digital and Ethernet line
100TX/100 Base-T
two RJ45 ports
max. range 20 m
100FX/100 Base-FX
two ports
LC connector
SFP transceiver 1,310 nm
max. range 1.5 km
Digital and digital line
Digital and FO line
Digital and analog line
t
≤ 5 ms
o
t
≤ 3 ms
o
P
< 10
-8
UC
P
< 10
-4
at BER of 10
-6
MC
14.3 Transmission Line - Digital Networks
X21 or G703.1
G703.6 sym. 120 Ω
G703.6 asym. 75 Ω