5.6 EN100 Firmware Upgrade

5.6
EN100 Firmware Upgrade
The firmware upgrade is not part of PU4 upgrade with Memtool. It is done in EN100 module homepage
according to following steps:
Open the upload page in the Web browser by entering the IP address of the module (see
²
example http://192.168.20.103/upload.
[ScUpload-28032014-1, 1, --_--]
Figure 5-52
Select the EN100 TPoP firmware image, which is located on the PowerSys Installation Path>\ PowerSys
²
\P3.5.xxx\Firmware\Package_xxx.cab\SWT_TPoP_Vxx.yy.zz.pck
The package_xxx.cab can be unzipped by any file archive tool, for example 7-Zip.
Click the Send File button. The page redirects you to the firmware update status
²
Click the refresh upload statistics link to check whether the upload is finished. If the page shows the
²
result as result: Update finished and progress: 100 percent, then the upload progress is done.
[ScFWStatus-28032014-1, 1, --_--]
Figure 5-53
248
EN100 Module Upload Page
EN100 Module Firmware Upload Status Page
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020