Signal Output From The Ifc-D/P Module - Siemens SWT 3000 Equipment Manual

Teleprotection system
Hide thumbs Also See for SWT 3000:
Table of Contents

Advertisement

[dwcsem34-051011-01.tif, 1, en_US]
Figure 8-8
(1)
Protective circuit
The protective circuit provides the required security against destruction and interference.
(2)
Setting of the input rated voltage
You can set the input rated voltage to the values DC 24 V, DC 48/60 V, DC 110 V, and DC 250 V
with the jumpers X43 to X58. The operating point is at 80 % of the selected voltage.
Refer to
(3)
Rectifier
Rectification ensures that the input signal is polarity-neutral.
(4)
Optocoupler
The optocoupler isolates the input circuit electrically from the electronic system.

Signal Output from the IFC-D/P Module

8.1.9
If there is an IFC-D module, the commands from the remote station are distributed via the relays K1 to K4. If
there is an IFC-P module, the commands from the remote station are distributed via the relays K13 to K16.
Compared with the IFC-P module, the relays of the IFC-D module are slower but they can switch more power.
[dwcsem35-051011-01.tif, 1, en_US]
Figure 8-9
K1 - K4
Output Relays of Module IFC-D
K13 - K16
Output Relays of Module IFC-P
D0 - D7
Operation of the IFCx Controller
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
Binary Inputs of Modules IFC-D and IFC-P
3.3.2.1 Overview
for more details
Block Diagram of the Output Circuit of IFC-D/P
Interface Command Module
8.1 General Information