Rm Configuration - Siemens SWT 3000 Equipment Manual

Teleprotection system
Hide thumbs Also See for SWT 3000:
Table of Contents

Advertisement

[scconsig-121011-01.tif, 1, en_US]
Figure 3-27
You can load a preset allocation by clicking on Default. All allocation settings are deleted by clicking the Clear
button.
When an IFC-S module is configured (as IFC-2 and/or IFC-4) the IFC-S signaling is automatically enabled with a
default allocation. The signaling allocation can be modified individually.
Unused command outputs of the Interface modules IFC-P, IFC-D or IFC-S can be flexible configured for
signaling outputs in all protection operating modes.

RM Configuration

3.5.8
Device data can be transmitted between the terminal devices of one or more SWT 3000 routes using RM. This
transmission makes it possible to import the parameter settings, the measuring points, and the event list of
the station from an SWT 3000 with the service PC.
The binary frequency shift keying (FSK) of the guard tone transmits the device data via the analog interface or
via the frame of the digital interface. The RM function is activated in the Configuration > RM dialog. The
device must also be assigned to an RM address.
For using the RM channel the Remote Maintenance check box must be activated.
For remote configuration via the RM channel, the Config. via inband RM-Channel: yes/no must be activated.
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
Configuration Menu Signaling Allocation, e.g. for Operating Mode 5D
Installation and Commissioning
3.5 Device Configuration
137