NOTE
i
i
If the SCD file does not contain the intAddr and daName tags for the inputs sections (so the substation
configurator does not provide this information), manual selection of the source and destination parameters
in the option table is necessary. Click the Source Parameter or Destination Parameter list box and select
the specific parameters.
When using the EN100 module, it is necessary to generate the EN100 parameter file (BIN file) and PowerSys
preconfiguration file (CFG file) and save them in a proper folder. The mentioned files can be uploaded to
PowerSys in the SWT 3000 > Configuration > System-2 submenu. Store the content of the BIN file then in PU4
Flash. With each startup of SWT 3000, the BIN file is transferred to volatile memory of the EN100 module.
In order to generate the desired Output files, define the name and place of storage of the Output files area
as follows:
Click the BIN File button.
The following dialog appears:
[scbinsel-080911-01.tif, 1, en_US]
Figure 5-67
Define the name and place of storage of the BIN file.
Afterwards, click Save.
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
Selection of Name and Place of the BIN File
PowerSys and Auxiliary Software Tools
5.8 MergeTool for IEC 61850
261