3.5.9.3

Timer Settings for the Command Output

[sclimout-300414-01.tif, 1, en_US]
Figure 3-35
Table 3-40
Selection
Limitation of output
command
The command in the following example is transmitted for 700 ms (Tx output). With the activated output limi-
tation, the command output is switched off after 500 ms.
[dwoutlim-150711-01.tif, 1, en_US]
Figure 3-36
(1)
Output limitation 500 ms
NOTE
i
i
Due to the limitation of 500 ms, an additional Rx-alarm occurs.
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
Setting Options for Limitation of the Output Command
Setting Options for Limiting or Increasing the Output Time
Setting Options
0 ms or 500 ms
Example of an Activated Output Command Limitation
Installation and Commissioning
3.5 Device Configuration
Comment
0 = no limitation
143