Command Outputs - Siemens CP 1243-1 Operating Instructions Manual

Communications processor for connecting the simatic s7-1200 to control center systems
Table of Contents

Advertisement

Range
Overflow
Overrange
Nominal range
(unipolar / life zero)
Nominal range (bipolar)
Underrange
(unipolar / life zero)
Underrange (bipolar)
Undershoot / wire break
Note
Evaluation of the value even when the option is disabled
If you enable one or both options and configure a value and then disable the option later, the
grayed out value is nevertheless evaluated.
To disable the two options, delete the previously configured values limit values from the input
boxes and then disable the relevant option.
Recommendation for quickly fluctuating analog values:
If the analog value fluctuates quickly, it may be useful to smooth the analog value first if limit
values are configured.
4.10.11

Command outputs

Parameters for command outputs
With the DNP3 and IEC protocols, the following parameters can be configured for command
outputs:
● LATCH_ON / LATCH_OFF
● PULSE_ON
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03
Raw value (16 bits) of the PLC tag
Decimal
Hexadecimal
32767
7FFF
32511
7EFF
...
27649
6C01
27648
6C00
...
0
0000
27648
6C00
...
0
0000
...
-27648
9400
-1
FFFF
...
-4864
ED00
-27649
93FF
...
-32512
8100
-32768
8000
Module output [mA]
0 .. 20
(unipolar)
> 23.515
23.515
...
...
20.001
20
...
...
0
...
...
-0.001
...
...
-3.518
...
< -3.518
Configuration
4.10 Data points
-20 .. +20
4 .. 20
(bipolar)
(life zero)
> 23.515
> 22.810
23.515
22.810
...
...
20.001
20.001
20
...
4
20
...
0
...
-20
3.999
...
1.185
-20.001
...
-23.516
< 1.185
Measuring
range [%]
> 117.593
117.593
...
100.004
100
...
0
100
...
0
...
-100
-0.004
...
-17.59
-100.004
...
-117.593
< -17.593
109