Unblocking Impulse Allocation For Ifc; T-Scheme Configuration - Siemens SWT 3000 Equipment Manual

Teleprotection system
Hide thumbs Also See for SWT 3000:
Table of Contents

Advertisement

Selection
Switch NU-Relay on
GAL
Alarm output
RXALR used for
3.5.14.5

Unblocking Impulse Allocation for IFC

Overview
The activated unblocking impulse (for more details refer to
connected via the IFC-D/P card when using the operating modes 1 and 2. When working with other operating
modes, the following system behavior must be observed:
Stand-alone Equipment
In the stand-alone unit, an activated unblocking impulse (t
5A) is executed via the RXALR relay on the ALR module. That means, there is no relay left for the receiver
alarm. The receiver alarm is indicated as general alarm GENALR.
SWT 3000 Integrated in the PowerLink System
The receiver alarm output of the PU4 module (RXALR) can be routed to the unblocking impulse in the service
program PowerSys (refer to
The RXALR output can be ranked to an alarm relay.
If there is an unblocking signaling via RXALR and ALR card, the active position of the relay must be considered
(an alarm is active when the relay is de-energized).

T-Scheme Configuration

3.5.15
Basic system configuration of T-scheme in SWT 3000:
Operation Mode
Connection
Special transmission
Special allocation
Address
Digital 1 and 2 could use different connection types. For example, digital 1 is an electrical and digital 2 is a
fiber-optic connection.
Command Allocation
The command input and output allocation is configured according to the user requirement.
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
Setting Options
Receiver alarm (RXALR)
Unblocking (UNBL)
Input limitation alarm (INPLIM)
Figure
3-56).
digital 1
digital 2
Transmitter
Receiver
Receiver 2
Comment
If there is a general alarm, non-urgent alarm
relay is additionally activated
Function deactivated (default setting)
Allocation of the receiver alarm to the alarm
output RXALR (default setting)
Allocation of the unblocking impulse to the
alarm output RXALR (for unblocking impulse.
Refer to
Table
3-37)
Allocation of the input limitation alarm to the
alarm output RXALR (for the adjustment of the
input limitation.
Refer to
Table
3-38)
2.7.2 Unblocking Mode
> 0) (in the operating modes 3, 3a, 3b, 4 and
unbl
Mode5D
X.21 or G.703 or FO
X.21 or G.703 or FO
T-scheme mode
off
<Own address>
<Remote address from LID-1 line>
Only possible in T-scheme mode.
<Remote address from LID-2 line>
Installation and Commissioning
3.5 Device Configuration
and to
Table
3-37) can be
167