Select Target > Setup in the menu bar and select the COM-Port of the Access Device "SWT 3000 PU4 CP2102
USB to UART Bridge Controller in the list box (for example COM6) in the General tab as follows:
[sctasege-020413-01.tif, 1, en_US]
Figure 5-35
Settings in the Setup > Monitor and Setup > Init tabs are defaults and remain unchanged.
NOTE
i
i
The baud rate in Setup > Monitor is set automatically according to the selected Target file (115 200 for
CSPi, 57 600 for vMUX and CSP, and 115 200 for PU4).
Manual changes are saved by clicking OK.
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
Target > Setup > General
PowerSys and Auxiliary Software Tools
5.4 MemTool Installation
233