Installation and Commissioning
3.5 Device Configuration
3.5.3.2

Line Interface

The menu option Connection analog or digital offers the following setting options:
Table 3-31
Connection Analog
off
CLE (only with system setting stand-alone)
via CSPi (dig)
FOM-1 analog
Table 3-32
Connection Ethernet
off
EN100-TPoP
Table 3-33
Connection Digital 1/2
X.21 DTE / DCE
G703.1 DTE / DCE
G703.6 DTE / DCE
FOM 64k DTE / DCE
FOM 2M DTE / DCE
FOBox 64k
FOBox 2M
C37.94-DTE / DCE
PU4 module types:
PU4-LIA for analog, digital and Ethernet interfaces
PU4-LID for digital and Ethernet interfaces only. It cannot be used as spare part of iSWT
If only digital or Ethernet interfaces are required in customer order, the PU4-LID board is delivered by produc-
tion.
In case of analog or mixed interfaces, the PU4-LIA board is delivered.
A primary and an optional, secondary connection interface for path redundancy can be configured.
By default, path redundancy is set according to priority as Digital 1 / 2 > Ethernet > Analog. In case of double
digital lines, 2 Mbps data rate > 64 kbps data rate.
Select Apply for the acceptance of all settings. If you click Cancel, the previous settings are retained. By
clicking OK, the settings are accepted and the input tab is closed.
NOTE
i
i
The digital fiber-optic interface can be adjusted to FOM_64k/2M-DCE/DTE, C37.94_DCE/DTE, FO-
Box_64k/2M. On the DLE module the X.21 jumpers must be selected.
Data rate 1/2
The data rate must be 1 to 12 x 64 kbps. For C37.94 DTE, it is also possible to detect the data rate of the DCE
device automatically by selecting Auto in the data rate field.
126
Setting Options for Analog Connection of the PU4 Module
Setting Options for Ethernet Connection of SWT 3000 devices
Setting Options for Digital Connection of the PU4 Module
Comment
Digital interface X.21 DTE or DCE
Digital interface G703.1 64 kbps DTE or DCE
Digital interface G703.6 2 Mbps DTE or DCE
Fiber-optic connection between 2 SWT 3000 with 64 kbps
Fiber-optic connection between 2 SWT 3000 with 2 Mbps
Fiber-optic connection to the FOBox bit rate 64 kbps
Fiber-optic connection to the FOBox bit rate 2 Mbps
Fiber-optic connection between 2 SWT 3000 with C37.94 protocol
Comment
No analog interface
Stand-alone devices with cable connection, or connection
to a Siemens PLC system via the CLE module
If integrated in the PowerLink system
Stand-alone device with FOM connection to a PowerLink
system
Comment
No Ethernet connection
Ethernet line interface via EN100-TPoP