Installation and Commissioning
3.5 Device Configuration
•
Any free relay contacts of command module IFC-D/P
•
Eight relay contacts of command module IFC-S
•
Three relay contacts of alarm module ALR
The alarm output allocation for IFC is possible for operation mode 3a / 3b / 5D.
Enable Signaling Output
IFC relay output assignment for command ack. signaling:
•
IFC-1 relay output 2 : ack. signaling of command output 1
•
IFC-1 relay output 3 : ack. signaling of command input 1
•
IFC-2 relay output 2 : ack. signaling of command output 2
•
IFC-2 relay output 3 : ack. signaling of command input 2
•
Relay open indicates no signaling.
•
Relay close indicates ack. signaling.
IFC relay output assignment for alarm signaling:
•
IFC-1 relay output 4 : alarm signaling of IFC-1 alarm + General alarm (GEN) + Rx alarm
•
IFC-2 relay output 4 : alarm signaling of IFC-2 alarm + General alarm (GEN) + Rx alarm
•
Relay close indicates no alarm occurred.
•
Relay open indicates alarm is occurred.
164
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020