Connection To The Swt 3000 Target; Programming The Application Into The Flash Memory - Siemens SWT 3000 Equipment Manual

Teleprotection system
Hide thumbs Also See for SWT 3000:
Table of Contents

Advertisement

NOTE
i
i
Wrong target selection results in unsuccessful flash programming. Verify that the selected target is the
physically connected device.
Refer to
5.4.3.2 MemTool Settings

Connection to the SWT 3000 Target

5.5.3
The PU4 memory consists of an internal FLASH (on-chip flash) and an external FLASH module. Both are
programmed sequential with the same procedure.
For 764 KByte on-chip Program FLASH module, the sector table is created after determining the actual type
of the FLASH and clicking Connect.
Select 764 KByte on-chip Program FLASH (not ready) in the Flash/OTP - Memory Device list box.
Click Connect to establish a connection to the target SWT 3000 system. The sector list box contains now the
sector table of the selected FLASH module. The Connect button changes to Disconnect.
If the connection fails, reset the PU4 module and try again. For more detailed information, refer to
5.5.5 Trouble
Shooting.
[scdicosw-171011-01.tif, 1, en_US]
Figure 5-43

Programming the Application into the Flash Memory

5.5.4
Click Open File and select the AllInOne_PU4_Px.y.z.jnk.
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
to get more detailed information.
Dialog of the Connection to SWT 3000 for 764 KByte On-Chip Program FLASH
PowerSys and Auxiliary Software Tools
5.5 PU4 Firmware Upgrade with Mem Tool
241