Interface
G703.6 symmetric
G703.6 asymmetric
3.3.4.4

Selection of the Input Gain for G703.6 Interfaces

This setting controls the sensitivity of the receive equalizer.
Table 3-22
Input gain
12 dB (for short haul)
43 dB (for long haul)
3.3.4.5

DLE Settings for the LID-x Connection via FOM

NOTE
i
i
If there is a connection of the LID-x via fiber-optic modules, always select the X.21 interface on the DLE
module.
When LID-x is connected via fiber-optic modules, no electrical cable must be connected at the corre-
sponding LID-x connector.

Jumper Settings for the CLE Module

3.3.5
[scclejum-301111-01.tif, 1, en_US]
Figure 3-10
Table 3-23
Setting
Input impedance
Output impedance
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
X48
23-24
33-34
25-26
33-34
Selection of the Input Gain for G703.6 Interfaces
LID-1
X53 / 2-3
X53 / 1-2
Position of the Jumpers on the CLE Module
Jumper Setting for the Input and Output Impedance
600 Ω
W4
W5
3.3 Jumper Settings for SWT 3000 Modules
X49
X46
X44
X7
23-24
1-2
2-3
2-3
33-34
23-24
2-3
1-2
1-2
33-34
LID-2
X52 / 2-3
X52 / 1-2
≥ 5 kΩ
Without W4
W6, W7, W8
Installation and Commissioning
X8
X9
X22
X23
2-3
2-3
2-3
2-3
1-2
1-2
1-2
1-2
115