Installation and Commissioning
3.3 Jumper Settings for SWT 3000 Modules
The second interface module is used in the case of an IFC-D/P module for doubling the output contacts. The
binary inputs are only connected to one module (in slot IFC-1 or IFC-3).
If the IFC-S module is used, jumpers X43 to X58 are not provided because the binary inputs do not exist.
The module contains 8 signaling relays. For 7 relays, one change-over contact is brought out in each case. The
contact of relay K5 can be used as a make contact or a break contact with jumper X42. All 8 signaling contacts
have a common root (3A1).
3.3.2.2

DIP Switches on IFC Modules

There are 2 Dual Inline Package (DIP) switches added to each IFC modules:
DIP switch S1 for the Test Mode.
The activated output relays are displayed with LEDs H1 to H4 (red), and the activated binary inputs with
LEDs H5 to H8 (green).
For more detailed information, refer to Interface Command
DIP switch S2 for the selection of PU3 and PU4 module and to indicate the slot address of each IFC
module.
For more detailed information, refer to
Table 3-16
Switch
Function
S2.1
IFC slot address selection
S2.2
IFC slot address selection
S2.3
PU3 or PU4 selection
S2.4
Not connected
Table 3-17
Selection
IFC-1
IFC-2
IFC-3
IFC-4
Table 3-18
Selection
PU3
PU4
!
CAUTION
Changing the position of an IFC module without changing its address may lead to a failure in the transmis-
sion.
The IFC module will be detected on a wrong slot. No information or wrong information may be trans-
mitted to the corresponding protection relay.
Make sure that the IFC module is in the right slot.
²
NOTE
i
i
The slots IFC-3 and IFC-4 are available only in PU4-mode of stand alone SWT 3000.
112
Function of S2 Switch
IFC Slot Address
S2.1 Position
Open = up position = OFF
Close = down position = ON
Open = up position = OFF
Close = down position = ON
PU3 or PU4 Selection
Module8.1.6.1
8.1.7 Slot and Module Identifier
S2.3 Position
Close = down position = ON
Open = up position = OFF
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
Overview.
.
S2.2 Position
Open = up position = OFF
Open = up position = OFF
Close = down position = ON
Close = down position = ON
C53000-G6040-C605-1, Edition 03.2020