AMP Meas Off or On
Disables the input limitation from the binary inputs (which is automatically activated in the AMP mode of
SWT 3000) when adjusted to on. It is now possible to send persistent commands for measuring the trip
frequencies.
If the AMP Meas is adjusted to on, the general alarm is activated.
Command delay test
Single test provides a method to measure command transmission time over the current active line. It is
available for both analog and digital transmission lines, but not for Ethernet transmission line (TPoP).
Reset SNMPv3 key
The key reset operation deletes all created SNMPv3 users, and new working users are cloned again from
the initial user template.
Clear CDB
The command clear configuration database (Clear CDB) clears the complete configuration stored in
the PU4 module. After the command is executed, you may receive hardware and/or configuration fault
alarm. If there is a new configuration from an existing SWT 3000 or after a firmware update, execute the
function to clear all former settings.
Reset device
Reset of the SWT 3000 via the service PC. After Reset device, the service program is automatically
connected back to the SWT 3000.
NOTE
i
i
The SWT 3000 can be monitored through the alarm output.