Integrated Into The Powerlink Plc System - Siemens SWT 3000 Equipment Manual

Teleprotection system
Hide thumbs Also See for SWT 3000:
Table of Contents

Advertisement

a)
One path via digital network; second path via 4-wire (or 2-wire)
b)
One path via power line and fiber optic; second path via fiber optic and digital network
Example 11:
SWT 3000 digital connections
The digital interface allows the transmission of the protection signals over a PDH or SDH network.
Alternative transmission routes
SWT 3000 enables transmission of protection signals via 2 different routes. Both routes are constantly used. If
one route fails, the second route immediately takes over without any loss of time.
Example 12:
Fiber-optic connections between SWT 3000 and PowerLink
A short-distance connection between an SWT 3000 and Siemens PowerLink PLC terminal can be realized via an
integrated fiber-optic module. In this case, an SWT 3000 stand-alone system provides the same advanced
functionality as the version integrated into PowerLink. Each PowerLink can be connected to 2 SWT 3000
devices via fiber-optics.
Alternative transmission routes
SWT 3000 enables transmission of protection signals via 2 different routes. Both routes are constantly used. If
one route fails, the second route immediately takes over without any loss of time.
Fiber-optic connection between SWT 3000 and a Multiplexer
A short-distance connection of up to 3 km between an SWT 3000 and a multiplexer can be realized via an inte-
grated C37.94 fiber-optic module.

Integrated Into the PowerLink PLC System

2.5.4
[dwintplc-211011-01.tif, 2, en_US]
Figure 2-7
a)
Power line
b)
One path via power line; second path via digital network.
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
Examples of Integrated SWT 3000
Functional Description
2.5 Possible Ways of Using the SWT 3000
47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents