Siemens SWT 3000 Equipment Manual page 73

Teleprotection system
Hide thumbs Also See for SWT 3000:
Table of Contents

Advertisement

ICD_IEC61850-Edition-1\*.ixd.
SWT 3000 IXD files for IEC 61850 Edition 1 with number of commands 1 to 8, and 16. It extends Siemens
proprietary elements based on the ICD file and is used only by MergeTool for both EN100 BIN and CFG file
generations. When selecting an ICD file in MergeTool, the related IXD file with the same number of
commands is selected implicitly.
ICD_IEC61850-Edition-2\*.icd.
SWT 3000 ICD files for IEC 61850 Edition 2 with number of commands 1 to 8, and 16.
ICD_IEC61850-Edition-2\*.ixd.
SWT 3000 IXD files for IEC 61850 Edition 2 with number of commands 1 to 8, and 16. It extends Siemens
proprietary elements based on the ICD file and is used only by MergeTool for both EN100 BIN and CFG file
generations. When selecting an ICD file in MergeTool, the related IXD file with the same number of
commands will be selected implicitly.
*.ifd file
EN100 interface setting file to configure HTTP/SNMP service and redundancy settings
To support more than 8 GOOSE commands, the ICD file swt3000_c16_ed1/2.icd shall be used. If the allocated
GOOSE commands are less than 16, the remaining commands still can be allocated to IFC-D/P board. This is
the so called "Mixed mode".
For IEC 61850 station with Edition 2, use the ICD files from folder ICD_IEC61850-Edition 2 in both DIGSI and
MergeTool. If EN100 module of SWT 3000 is parametrized correctly for IEC 61850 Edition 2, you find an entry
in EN100 startup log via the EN100 Web homepage, for example https://192.168.20.101/startuplog.
NOTE
i
i
+++ 00011 00179049 Su 2.01.1994 00:00:59:048 Starting in Edition 2 modus
Report and GOOSE
The LN ITPC (Teleprotection Communication Interfaces) comprises all information for communication channel
supervision. This information can be grouped in a dataset. A report is sent out if the status value or quality
attribute is changed.
GOOSE message is a peer-to-peer communication to transmit or receive protection commands between a
protection device and SWT 3000. In the SWT 3000 system, alarms (General, Rx and Non-urgent alarms) are
distributed via 3 relay contacts of ALR module. If IEC 61850 communication networks are used, these alarms
can also be distributed using GOOSE messages.
An example for a IEC 61850 system configuration is shown in
It is parameterized as shown below:
Report mapping of assignment of LN ITPC data attribute to data set.
GOOSE Mapping of protection commands between protection and SWT 3000
GOOSE Mapping of device failure alarm (ITPC.AlarmGen) from SWT 3000 to protection
Monitoring quality attribute of alarm GOOSE message in protection to indicate a IEC61850 communica-
tion link failure (e.g. using CFC block SI_GET_STATUS of DIGSI)
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
Figure
2-21.
Functional Description
2.11 IEC 61850
73