Siemens SWT 3000 Equipment Manual page 297

Teleprotection system
Hide thumbs Also See for SWT 3000:
Table of Contents

Advertisement

1
Coupling of 2 SWT 3000 routes
Protection signal transmission path
ETH
Ethernet interface (TCP/IP)
SSB
Remote monitoring interface
RM
Inband RM-Channel
If Service PC is connected to
distant SWT 3000 (address 2,
3 or 4)
If RM data transmission is
active in distant SWT 3000 via
SSB (address 3 or 4)
The SSB interface of the SWT 3000 system has the same characteristics as the RM-2 interface of the PowerLink
systems.
The following figure shows the remote connection to the SWT 3000 in station A via TCP/IP connection. The
access to the SWT 3000 devices in station B and C is possible when the inband RM-Channel is activated.
[dwconrmf-080611-01.tif, 1, en_US]
Figure 6-28
1
Master and slave connection with crossed cable
Protection signal transmission path
SC
Service channel
ETH
Ethernet interface (TCP/IP)
USB
Local interface
SSB
Remote monitoring interface
RM
Inband RM-Channel
Use a crossed cable for the SSB to SSB connection in station B (refer to
Configure one of the SSB interfaces as Slave and the other one as Master.
For the service program PowerSys connection, select Remote Device in the Data Source menu or use the
corresponding button (Data Source Remote Device) in the menu bar as follows:
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
Activation of an SSB data transmission from another SWT 3000 is possible
without influencing the service PC connection at the Ethernet (ETH) or local
(USB) interface. Because the SSB connection is the second one, only read
permission is available, while the first connection (service PC) has read and
write access.
Connection of the service PC to the Ethernet (ETH) or local (USB) interface
does not block the SSB transmission. Because the connection is the second
one, only read permission is available, while the first connection (SSB) has
read and write access (if configured).
Connection to SWT 3000 in Station B and C with the RM Function
SNMP and Remote Access
6.3 Remote Access
3.2.7 Pinout of the SSB
interface).