Siemens SWT 3000 Equipment Manual page 141

Teleprotection system
Hide thumbs Also See for SWT 3000:
Table of Contents

Advertisement

[dwinplim-150711-01.tif, 1, en_US]
Figure 3-31
(1)
Input limitation 50 ms
Table 3-39
Selection
Input command extension
min.
If the commands at the binary input are shorter, they are extended to adjusted value. If they are longer, this
adjustment is irrelevant.
The following figure shows one command (red) at the binary input with a length of 10 ms. This command is
extended to 15 ms. The next command (blue) has a length of 30 ms. This command is not extended.
[dwinpext-130911-01.tif, 1, en_US]
Figure 3-32
(1)
Input Extension to minimum 15 ms
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
Example for Input Limitation Set to 50 ms
Setting Options for Input Command Extension to Minimum
Setting Options
0 ms to 100 ms
In steps of 1 ms
Example for an Input Command Extension to Minimum 15 ms
Installation and Commissioning
3.5 Device Configuration
Comment
0 = no extension
Default = 15 ms
141