Diagnostics and Error Handling
4.5 Display of the Entries in the Event Recorder
Display of the Entries in the Event Recorder
The following figure shows the contents of an event recorder:
[scevente-091111-01.tif, 1, en_US]
Figure 4-12
In the first 4 lines, the fixed records are displayed without event number.
Table 4-10
No.
Grp
1
1
2
3
3
3
4
3
Each record is marked with [Date] (year.month.day), [Time] (hour:minute:second.hundredth.thousandth),
[Grp] (group identifier), [Evt] (event identifier), and [Description]. The event record numbers [No] are
entered from the PU4 module from 0 to 9999. After 9999, the event-counter restarts with 0.
For a better understanding of the event-recorder entries, set the time and date on the PU4 with PowerSys
before starting operation. During power off, time and date are saved on the PU4 for about 96 hours. The
recorded event entries are non volatile.
Table 4-11
Grp
1
2
3
4
128 to 255
192
Entries in the SWT 3000 Event Recorder
Fixed entries in the event recorder
Evt
Description
1
Last start-up of the PU4 firmware
20
Last successful clock synchronization (if activated)
25
Last change of the device data (not date or time change!)
90
Last change of the line selection to LIA
91
Last change of the line selection to LID1
92
Last change of the line selection to LID2
Group Numbers
Description
System control
Teleprotection commands
Alarms
Alarms
Internal system messages
Smart Communication, SWT 3000 Teleprotection, Equipment Manual