SNMP and Remote Access
6.2 SNMP
After having been successfully connected to the SNMPv3 agent, the initial users are listed as follows:
[scuserop-140912-01.tif, 1, en_US]
Figure 6-7
Table 6-5
Operation
Clone User
Enable User
Change Authentication Password
Change Privacy Password
Disable User
Delete User
NOTE
i
i
Because the initial user name and password are printed on paper and are well known for other people, you
must create at least one working user from the initial user template, change the default authentication,
and the privacy password as soon as possible. After all needed working users are created, the initial and
template users should be deleted.
Example: Create New User
This example shows the workflow of creating a new user "testuser" using iReasoning MIB Browser.
1 - Open the SNMPv3 user management tool from MIB Browser.
2 - All users of the remote agent are listed in the user management tool.
3 - Select the user template you want to clone from:
templateMD5: user template with MD5 authentication protocol and DES privacy protocol
templateSHA: user template with SHA authentication protocol and DES privacy protocol.
4 - Click on clone user operation and enter a new user name in the text box.
282
USM User Operation
USM User Table
Comments
Create new SNMPv3 users from existing one.
Enable a disabled SNMPv3 user.
Change the authentication password to a new one.
Change the privacy password to a new one.
Disable the active SNMPv3 user and change the row status from
"active(1)" to "notInService(2)".
Delete the existing SNMPv3 user.