Installation and Commissioning
3.5 Device Configuration
[scrmconf-121011-01.tif, 1, en_US]
Figure 3-28
Table 3-36
Menu Option
Remote Maintenance
Device Address
Interface RM
Interface SSB
Config. via inband RM-Channel:
yes/no
NOTE
i
i
If Continuous signaling is configured (refer to Chapter
Path), Remote Maintenance cannot be activated.
138
Configuration > RM Dialog
Setting Options for RM Configuration
Setting
Comment
Options
RM activated
RM deactivated
0 to 249
RM address
Master
Setting remote station Slave
Slave
Setting remote station Master
Master
Setting remote station Slave
Slave
Setting remote station Master
Configuration of the remote device via RM
channel enabled
Configuration of the remote device via RM
channel disabled
3.5.3.5 Continuous Signaling (Analog Transmission
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020