Siemens SWT 3000 Equipment Manual page 144

Teleprotection system
Hide thumbs Also See for SWT 3000:
Table of Contents

Advertisement

Installation and Commissioning
3.5 Device Configuration
[scoutext-121011-01.tif, 1, en_US]
Figure 3-37
Table 3-41
Selection
Output command extension
The command in the following example is transmitted for 50 ms (Tx output). With the output command
extension on the Rx output, the command is extended for 200 ms.
[dwoutext-150711-01.tif, 1, en_US]
Figure 3-38
(1)
Output extension 200 ms
144
Setting Options for the Output Command Extension
Setting Options for the Output Command Extension
Setting Options
0 ms to 2000 ms
In steps of 5 ms
Example for an Output Extension of 200 ms
Comment
-
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020