Table 6-11
Settings
Index
IP-Address
Community String
UDP Port
Enabled
Send
Reset
The NMS addresses as well as the community string for SNMP get or set command must be adjusted via web
logon and must match between the SNMP agent and the NMS.
6.2.4.3

Access Password

Within this menu, you can set the SNMP read-only and read-write community string. The read-write
community string can also be used as the password for web login.
[scaccpas-300414-01, 1, en_US]
Figure 6-21
11
Range for UDP Port: 0 to 65 535, but well known ports up to 1023 must not be used. Exception for SNMP: Port 161: get and set, Port
162: traps
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
SNMP V2 Trap-Destination Table
Comments
1 to 6
IP address of trap destination (NMS)
Actual community string
Must be identically with the community string in the NMS
Range: from 1024 to 65 535
Default: 162 (well known port for traps)
Must be identically with the number in the NMS
On ( ) or off ( )
Default: off (
Send the values to the PU4 module.
Reject the changes.
Access Password
SNMP and Remote Access
11
6.2 SNMP
291