Installation and Commissioning
3.5 Device Configuration
Table 3-34
Slot
IFC-1
IFC-2
IFC-3
IFC-4
GOOSE Command Interface
When the EN100 module is equipped, generate the preconfiguration file (CFG) and the EN100 parameter file
(BIN) using the MergeTool. For more information about IEC 61850 configuration in MergeTool and DIGSI refer
to
5.8.2 Parameter
In order to activate the System-2 Configuration > EN100, select the EN100
Click on PowerSys Pre-Config to upload the CFG file.
The following dialog appears:
[scselcfg-080911-01.tif, 1, en_US]
Figure 3-21
Select the proper CFG File from the database.
Click Open.
Click the EN100 Parameter File button to upload the BIN file.
The following dialog appears:
130
Equipment Options for Slots IFC-1 to IFC-4
Equipment
Application
IFC-D or IFC-P
Command input/command output
IFC-D, IFC-P, or IFC-S Doubling of command output contacts or status messages slot IFC-1.
Command input/command output only with digital interfaces.
IFC-D or IFC-P
Command input/command output
IFC-D, IFC-P, or IFC-S Doubling of command output contacts or status messages slot IFC-3.
Command input/command output only with digital interfaces.
Generator.
Selection of the CFG File
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020