System Configuration; Operating Mode - Siemens SWT 3000 Equipment Manual

Teleprotection system
Hide thumbs Also See for SWT 3000:
Table of Contents

Advertisement

System Configuration

3.5.3
3.5.3.1

Operating Mode

[scconmen-300414-01.tif, 1, en_US]
Figure 3-18
Table 3-30
Operating mode
Mode 1 (double system protection)
Mode 2 (single phase protection)
Mode 3 (switching functions)
Mode 3a (4 independent commands)
Mode 3b (2 plus 2)
Mode 4 (only one command active)
Mode 5A (3 independent commands)
Mode 5D
Set the System mode as follows:
Select stand-alone for a stand-alone device.
Select integrated in PowerLink for a device integrated in PowerLink.
If the SWT 3000 device is not integrated in PowerLink, it is possible to configure the device as stand-alone.
On the other hand, if the device is inserted in PowerLink (iSWT), the system mode must be fixed as integrated
in PowerLink and allows no change.
The teleprotection signaling parameter is set as single purpose for stand-alone devices. The setting alternate
multi-purpose is also possible with a Siemens PLC system depending on the configuration and parameters of
the Siemens PLC system.
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
Dialog for the SWT 3000 System Configuration
Selection of the Operating Modes
Comment
Possible with all variants
Possible with all variants
Possible with all variants except VF1_CT and VF3_CT
Only possible with the variants VF1_CT or VF3_CT
Only possible with the variants VF1_CT or VF3_CT
Possible with all variants
Only possible with the variant VF1 M5A or VF3 M5A
Only for digital transmission paths
Installation and Commissioning
3.5 Device Configuration
125