Wiring test

active = Yes
Workflow
Wiring test
active = No
88/148
Siemens Building Technologies
HVAC Products
5.2 Wiring test

5.2.1 Wiring test active "Yes / No"

The reference data point "Wiring test active" is displayed only if the reference data point
"Commissioning mode = On" is set.
1.
Select
Applications > Popcard...
2.
In the menu tree, select
3.
Double-click "Wiring test active" to open a dialog box. Select
to enter the value.
OK
After you complete the wiring and communication tests, you must reset the reference
data point to "Wiring test active = No".
Commissioning instructions OZW775 V2.01
Further commissioning steps
and check for "Commissioning mode = On".
and reference data point "Wiring test active".
Wiring test
Yes
and click
CE1C5663en