Jumper Settings For The Dle Module; Overview; Jumper Settings For The Selection Of Digital Line Interfaces Lid-1; Jumper Settings For The Selection Of Digital Line Interfaces Lid-2 - Siemens SWT 3000 Equipment Manual

Teleprotection system
Hide thumbs Also See for SWT 3000:
Table of Contents

Advertisement

Installation and Commissioning
3.3 Jumper Settings for SWT 3000 Modules

Jumper Settings for the DLE Module

3.3.4
3.3.4.1

Overview

When using digital line interfaces, links must be set on the DLE module. Module DLE is designed as a self-
contained PC board that is connected electrically to the PU4 via a ribbon cable and mechanically via spacer
sleeves. All external interfaces are routed via the PU4 module.
[scdlejum-301111-01.tif, 1, en_US]
Figure 3-9
3.3.4.2

Jumper Settings for the Selection of Digital Line Interfaces LID-1

Table 3-20
Interface
X.21
G703.1
G703.6 symmetric
G703.6 asymmetric
3.3.4.3

Jumper Settings for the Selection of Digital Line Interfaces LID-2

Table 3-21
Interface
X.21
G703.1
114
Position of the Jumpers on the DLE Module
Interface Selection for the LID-1
X48
1-2
11-12
3-4
13-14
5-6
15-16
7-8
15-16
Interface Selection for the LID-2
X48
19-20
29-30
21-22
31-32
X49
X42
X43
X6
1-2
1-2
2-3
2-3
11-12
3-4
1-2
2-3
2-3
13-14
5-6
1-2
2-3
2-3
15-16
5-6
2-3
1-2
1-2
15-16
X49
X46
X44
X7
19-20
1-2
2-3
2-3
29-30
21-22
1-2
2-3
2-3
31-32
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020
X4
X5
X20
X21
2-3
2-3
1-2
1-2
2-3
2-3
2-3
2-3
2-3
2-3
2-3
2-3
1-2
1-2
1-2
1-2
X8
X9
X22
X23
2-3
2-3
1-2
1-2
2-3
2-3
2-3
2-3