Siemens SWT 3000 Equipment Manual page 310

Teleprotection system
Hide thumbs Also See for SWT 3000:
Table of Contents

Advertisement

Processing Unit Module
7.1 Functions of the PU4 module
[dwbliswt-051011-01.tif, 2, en_US]
Figure 7-2
IFC
Interface command module
PU4
Processing unit module
LIA
Analog line interface
DLE
Digital line equipment
LID
Digital line interface
EN100
Ethernet EN100 module for IEC 61850
SSI
Serial synchronous interface
iLAN
Internal LAN
CSPi
Central signal processing unit
PS
Power supply
At the receive side, the incoming commands are received in the VF range or digital depending on the oper-
ating mode.
These commands are converted into one of the following cases:
Binary protection commands, and forwarded to the IFC-D/P module for command output.
GOOSE command and forwarded to EN100 module for command output
Apart from coding and decoding of protection commands, the PU4 also performs various monitoring func-
tions.
For example, the receive and transmit levels are fed via measuring points to the PU4 where they are compared
with the permissible values. If these levels are not reached, the PU4 activates an alarm. In the normal situa-
tion, that is, if there is no protection command transmitted, the guard signal is sent to the remote station.
Loss of a wanted signal (command or guard tone) triggers a receive alarm at the receive side and causes the
relay outputs of the device to block. This alarm state can only be canceled by receiving the guard signal again.
310
Block Diagram of the SWT 3000 Unit Integrated in the PowerLink
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020