5.2.3.2

Voltage Measurement

Pos : 26.19 /Serie 761 (T O-PASS)/Ansc hliessen/Ansc hluss beispi eleHi nweis : Spannungs mess ung nur über U/I- Wandler @ 7\mod_1265647550343_21.doc x @ 50060 @ @ 1
Voltage measurement can only be performed via U/I transformer!
Voltage measurement cannot be performed via multiplier at the analog inputs,
since the internal resistance of the TO-PASS
input current.
WAGO 857 Series JUMPFLEX Isolation Amplifiers for level conversion may be
used for voltage measurement via TO-PASS
Pos : 26.20 /Serie 761 (T O-PASS)/Ansc hliessen/Ansc hluss beispi ele/Ansc hlus sbeispi el 761-31x 4AI U - Abbildung @ 15\mod_1365081727789_21.doc x @ 116547 @ @ 1
Figure 17: Connection example for voltage measurement via U/I converter at input AI1
Pos : 26.21 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
WAGO-TO-PASS® 761
761-314 TO-PASS® Mobile, 4 AI
®
telecontrol module depends on the
®
telecontrol modules.
Manual
Version 2.0.0