Voltage Measurement; Figure 16: Connection Example For Voltage Measurement Via U/I Converter At - WAGO 761-113 Manual

Telecontrol module compact, 2 ai, web for wago-to-pass 761. telecontrol module for fault detection/indication, monitoring and remote control.
Table of Contents

Advertisement

40
Connect Devices
5.2.3.2

Voltage Measurement

Voltage measurement can only be performed via U/I transformer!
Voltage measurement cannot be performed via multiplier at the analog inputs,
since the internal resistance of the TO-PASS
input current.
WAGO 857 Series JUMPFLEX Isolation Amplifiers for level conversion may be
used for voltage measurement via TO-PASS
Figure 16: Connection example for voltage measurement via U/I converter at input AI1
761-113 Telecontrol Module Compact, 2 AI, Web
®
telecontrol module depends on the
®
telecontrol modules.
WAGO-TO-PASS® 761
Manual
Version 2.0.0