8.2 Fault and system messages

Damage caused by incorrect parameter assignment
Malfunctions can occur if you change parameters.
● Do not change the parameters, e.g. for the motor circuit-breaker.
Note
To complement these operating instructions, the List Manual contains an overview of all
parameters as well as a selection of function diagrams to describe the operating principle.
8.2
Fault and system messages
8.2.1

Diagnostics

8.2.1.1

Diagnostics via LEDs

LEDs of the Power Stack Adapters
Table 8-1
LEDs of the Power Stack Adapters
LED
Color
PWR
-
Red
Green
72
Status
Description; cause
Off
24 V power supply has failed or is too low
(< 14 V) or internal fuse defective.
Continuous
24 V power supply is available (>14 V);
light
internal board voltage fault.
Continuous
24 V power supply OK.
light
Internal board voltages OK.
Remedy
Check input voltage.
If input voltage is > 18 V and LED off:
Return component for repair.
Check input voltage.
If input voltage is > 18 V and LED red:
Return component for repair.
--