Diagnostics via LEDs

LEDs of the Power Stack Adapters
Table 8-4
LEDs of the Power Stack Adapters
LED
Color
PWR
-
Red
Green
RUN /
-
ERR
Green
Orange
Red
Green/red
Green/
orange
or
Red/orange
8.6.3.3

Diagnostics via parameters

Diagnostic parameters for the device status
r0002
Drive status
Display of drive status
SINAMICS SM150 6SL3845-7NN42-2AA3 HBIS Shigang WRM NTM
Operating Instructions Rev.202003051222 3005356504
Status
Description; cause
Off
24 V power supply has failed or is too low
(< 14 V) or internal fuse defective.
Continuous
24 V power supply is available (>14 V);
light
internal board voltage fault.
Continuous
24 V power supply OK.
light
Internal board voltages OK.
Off
The electronic power supply is missing or
lies outside the permissible tolerance
range.
Continuous
The component is ready for operation
light
and cyclic DRIVE-CLiQ communication
is in progress.
Continuous
DRIVE-CLiQ communication is being es‐
light
tablished.
Continuous
At least one fault is present in the com‐
light
ponent.
LED is controlled irrespective of the cor‐
responding messages being reconfig‐
ured.
0.5 Hz flashing
Firmware download in progress.
light
2 Hz flashing
Firmware download is complete. Waiting
light
for POWER ON.
Flashing light
Component recognition via LED is acti‐
vated.
The color depends on the LED state
when component recognition is activated.
8.6 Fault and system messages
Remedy
Check input voltage.
If input voltage is > 18 V and LED off:
Return component for repair.
Check input voltage.
If input voltage is > 18 V and LED red:
Return component for repair.
--
-
-
-
Remedy and acknowledge fault.
-
Carry out a POWER ON.
-
Operation