Flowchart B: V/F Motor Control Set-Up - YASKAWA V1000 Series Installation & Start-Up Manual

Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

4.3 Start-up Flowcharts

Flowchart B: V/F Motor Control Set-Up

Figure 4.7
describes how to operate the application in V/f Control. V/f Motor
Control is suited for the most basic applications such as fans or pumps. This
procedure provides quick set-up using only the most basic parameters. V/f control
can be used where rotational auto-tuning cannot be performed.
Figure 4.7
Perform Stationary Auto-Tuning
* b1-01, b1-02 for frequency reference and run command source
* H1-xx, H2-xx, H3-xx, H4-xx, H6-xx to configure the analog/digital
I/O terminals.
* d1-xx speed reference values if necessary
* C1-xx, C2-xx for Acceleration/Deceleration times and S-curves
* C6-01 Duty Mode
120
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Set A1-02 for V/f Control A1-02=0.
Set or verify the V/f pattern E1-03.
NO
Is the cable
between the motor and
drive longer than 50 m?
YES
for terminal resistance only.
Use parameter A1-06 (application selection) for basic application
manually set/check the basic parameters:
Run the motor without the load.
Couple the load or machine to the motor. Run the drive and motor
and check direction and operation
Fine tune and set application parameters (e.g. PID,...) if necessary.
Check system operation and verify settings function as required.
Drive is ready to run the application
Figure 4.7 V/f Control
Does the application
need Speed-Estimation
Type Speed Search?
YES
(b3-24 = 1)
Perform Auto-Tuning
for Energy Savings in V/f
(motor rotates).
NO
NO
setup
OR

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents