8400 StateLine C | Reference manual
Function library
Function blocks | L_MPot_1
16.1.23.2
Deactivate motor potentiometer
When the motor potentiometer is deactivated by setting bInAct to TRUE, the nOut_a
output signal responds according to the function selected via Function.
When the motor potentiometer is deactivated, nOut_a is reduced to 0 % with the deceleration time wTif.
If it is activated again, nOut_a is increased again to nLowLimit with the acceleration time wTir.
[16-12] Example: Deactivation of the motor potentiometer when the Function = 1 has been selected
812
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
nOut_a
nHighLimit
wTif
0
nLowLimit
wTif
0
bUp
TRUE
FALSE
bDown
TRUE
FALSE
bInAct
TRUE
FALSE
L
1
wTif
wTir
wTir
t
t
t
t
Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011