5.6.2.1
Parameterising the slip regulator
The slip regulator is designed as a PI controller. In order to improve the response to setpoint
changes, the setpoint speed or setpoint frequency is added to the output (correcting
variable) of the slip regulator as feedforward control value.
In contrast to the conventional speed controller, the slip regulator only regulates the
slip.
In the Lenze setting, the slip regulator features a configuration with a goof robustness
and moderate dynamics.
Parameter
C00971/1
C00971/2
C00972
C00973
Slip regulator gain Vp
The setting range of the slip regulator gain Vp (C00972) which leads to a stable operational
performance, mainly depends on the resolution of the speed sensor. There is a direct
relationship between encoder resolution and gain:
The higher the encoder resolution, the higher the gain can be set.
The following table provides maximum and recommended slip regulator gains for encoder
with standard encoder increments:
Encoder increment
[Increments/revolution]
8
64
100
120
128
256
386
512
640
768
896
1014
1536
2048
3072
4096
[5-1]
Slip regulator gain Vp based on the encoder increment
Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Info
VFC: Controller limitation V/f +encoder
VFC: Slip limitation V/f +encoder
VFC: Vp V/f +encoder
VFC: Ti V/f +encoder
Slip regulator gain Vp
maximum
0,09
0,52
0,79
0,94
1,00
1,29
1,63
1,97
2,31
2,65
2,99
3,33
4,69
6,05
8,77
11,49
L
8400 StateLine C | Reference manual
V/f control (VFCplus + encoder)
recommended
0,06
0,31
0,47
0,57
0,60
0,77
0,98
1,18
1,38
1,59
1,79
2,00
2,81
3,63
5,26
6,90
Motor control (MCTRL)
Lenze setting
Value Unit
10.00 Hz
100.00 Hz
0.100 Hz/Hz
100.0 ms
157