8400 StateLine C | Reference manual
Motor control (MCTRL)
Parameterisable additional functions
5.9.7.1

Oscillation damping voltage range

The oscillation damping voltage range is successfully used with
 unloaded motors (no-load oscillations)
 motors whose rated power deviates from the rated power of the controller.
– e.g. during operation at high switching frequency including the power derating
involved.
 operation with higher-pole motors
 operation with special motors
 compensation of resonance in the drive
– At an output frequency of approx. 20 ... 40 Hz, some asynchronous motors can show
resonance which causes current and speed variations and thus destabilise the
running operation.
Parameter
C00234
C00235
Note!
Compensate the resonance during operation with feedback (closed loop,
feedback of n
Parameterising the slip regulator
How to eliminate speed oscillations in no-load operation at speeds with 40 ... 80 %
of the rated speed:
1. Approach the area where the speed oscillations occur.
2. Reduce the speed oscillations by changing
• The filter time oscillation damping (C00235) should not be changed.
3. These can be indicators for smooth running:
• Constant motor current characteristic
• Reduction of the mechanical oscillations in the bearing seat
210
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Info
Oscillation damping influence
Oscillation damping filter time
) via the parameters of the slip regulator.
act
L
( 157)
C00234
step by step (increment 1 %).
Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011
Lenze setting
Value Unit
5.00 %
32 ms