Maximum Torque Monitoring - Lenze 8400 StateLine C Reference Manual

L-force drives; e84avsc series;
Hide thumbs Also See for 8400 StateLine C:
Table of Contents

Advertisement

5.12.9

Maximum torque monitoring

This function extension is only available from version 04.00.00!
Note!
In the Lenze setting
monitoring is not activated!
If the maximum possible torque
C00608
will be carried out (Lenze setting: "0: No response").
If the activated monitoring is tripped:
 The
"OT1: Maximum torque
 The bMctrlTorqueMax status output of the
to TRUE.
5.12.10
Motor speed monitoring
This function extension is available from version 11.00.00!
If the drive reaches the maximally permissible motor speed (C00965):
 The "Fault" error response takes place, i.e. the motor is shut down immediately.
 The error message
Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
8400 StateLine C | Reference manual
(C00608
= "0: No response"), the maximum torque
C00057
is reached at the motor shaft, the response set in
reached" error message is entered into the logbook.
"OS2: Max. motor speed
L
Motor control (MCTRL)
LS_DeviceMonitor
system block will be set
reached" is entered into the logbook.
Monitoring
243