Commissioning - Lenze 8400 StateLine C Reference Manual

L-force drives; e84avsc series;
Hide thumbs Also See for 8400 StateLine C:
Table of Contents

Advertisement

3

Commissioning

Danger!
Uncontrolled motor movements can occur
Under certain conditions the motor may rotate after mains connection.
Possible consequences:
• Persons in the vicinity of the machine or plant risk getting hurt.
• Unexpected starting action may damage the machine or plant.
Protective measures:
• Commissioning with external 24 V supply and without mains voltage. In this
case, the controller can only be parameterised and diagnosed during
commissioning.
• Ensure that setpoints are not active.
Tip!
• Information on some of the operating statuses can quickly be obtained via the
LED status displays
• Check firmware: Particularly with regard to the use of older controllers (e.g. if
the customer is using one from stock) it makes sense to check the software
(firmware) version. The software version of the controller can be seen on the
nameplate in the "SW" line and can be determined by reading out code C00099.
• Restore delivery status: Set code
parameter settings of the device to the Lenze setting. This leaves you with a
defined device configuration.
The following chapters describe the commissioning of the available technology
applications with the »Engineer«.
Information on the commissioning with the keypad (diagnosis terminal) is
provided in the 8400 hardware manual.
• The hardware manual has been stored in electronic form on the data carrier
supplied with the 8400 drive controller.
Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
8400 StateLine C | Reference manual
on the front of the controller.
C00002/1
Load Lenze setting
L
Commissioning
( 381)
to "1: On / start" to reset all
( 79)
47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents