8400 StateLine C | Reference manual
Technology applications
TA "Switch-off positioning"
7.3.4

Process data assignment for fieldbus communication

The fieldbus communication is connected (preconfigured) to the previously selected
technology application by selecting the corresponding control mode in C00007:
 "30: CAN" for the connection to the system bus (CAN)
 "40: MCI" for the connection to a plugged-on communication module (e.g. PROFIBUS)
The assignment of the process data words does not depend on the applied bus system but
exclusively on the application:
Input words
Word 1 DriveControl
Word 2 MainSetValue
Word 3 -
Word 4 -
Word 5 ... 16 -
Control word
338
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Name
Name
Bit 0 SwitchOn
Bit 1 DisableVoltage
Bit 2 SetQuickStop
Bit 3 EnableOperation
Bit 4 ModeSpecific_1
Bit 5 JogCtrlInputSel1
Bit 6 JogCtrlInputSel2
Bit 7 ResetFault
Bit 8 bJogCtrlRfgIn
Bit 9 reserved_1
Bit 10 reserved_2
L
Assignment
Control word
• See table below for bit assignment.
Speed setpoint
• Scaling: 16384 ≡ 100 % reference speed (C00011)
Not preconfigured
Not preconfigured
Not preconfigured
• Only available for control mode "40: MCI".
Function
1 ≡ Change to the "SwitchedOn" device status
• This bit must be set in the CAN/MCI control word to ensure
that the device changes to the "SwitchedOn" device status
after mains connection without the need for a master control
specifying this bit via fieldbus.
• If control via a bus system is not wanted (e.g. in the case of
control via terminals), the wDriveCtrl output signal of the
LS_ParFix
system block can be connected to the control word
inputs.
1 ≡ Inhibit inverter control (IMP - pulse inhibit)
1 ≡ Activate quick stop (QSP).
Activate/Deactivate quick stop ( 83)
1 ≡ Enable controller (RFR)
• If control via terminals is performed, this bit must be set both
in the CAN control word and in the MCI control word.
Otherwise, the controller is inhibited.
Enable/Inhibit controller ( 82)
Reserved (currently not assigned)
Binary coded selection of the switch-off position 1 ... 3
• Activation of the signal pairs
bJogCtrlSlowDown1/bJogCtrlStop1,
bJogCtrlSlowDown2/bJogCtrlStop2 or
bJogCtrlSlowDown3/bJogCtrlStop3 according to the
table for activating the pre-switch
1 ≡ Reset fault (trip reset)
• Acknowledge fault message (if the error cause has been
eliminated).
Reset error ( 84)
Ramping down of the setpoint generator in the
downstream
L_NSet
FB according to the
activating the pre-switch off
Reserved (currently not assigned)
Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011
Truth
off.
Truth table for