Field weakening for synchronous motors

This function extension is available from version 11.00.00!
Note!
Function only available for sensorless control for synchronous motors (SLPSM)
(from version
In the Lenze setting, the field weakening for synchronous motors is set in
C00079/4.
• If a high energy efficiency is required, keep the field weakening switched off
or restrict the field weakening operation via C00938.
Stop!
In the field weakening operation, a current is injected into the synchronous
motor even in idle state which can rise to maximum current (C00022).
Ensure that this no-load current does not cause the motor to be heated
impermissibly!
• We recommend using a temperature feedback via PTC or thermal contact.
U
motor
Œ
Armature control range
Field weakening range
[5-21] Voltage/speed characteristic with switched-on field weakening
[5-22] Calculation of the maximally reachable speed with switched-on field weakening
Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
10.00.00).
Motor temperature monitoring (PTC)
 When field weakening is switched on, the motor
magnetising current is increased from 0 A to the
maximally effective magnetising current via an
internal control loop when the voltage limit is
reached.
 As a result, a higher speed can be reached at the same
motor voltage or DC-bus voltage.

n
n
n
=
max
L
8400 StateLine C | Reference manual
Parameterisable additional functions
( 236)
800V
------------------------------------- -
nenn_mot
2 U
nenn_mot
Motor control (MCTRL)
213