Activate & control motor potentiometer
When bInAct is set to FALSE, the motor potentiometer is activated.
 The currently active function depends on the current output signal nOut_a, the limit
values set and the control signals at bUp and bDown.
 When the nOut_a output signal is outside the limits set, the output signal runs to the
next limit with the Ti times set. This process is independent of the control signals at
bUp and bDown.
 When the nOut_a output signal is inside the limits set, the output signal changes
according to the control signals at bUp and bDown.
[16-11] Example: Control of the motor potentiometer
bUp
FALSE
TRUE
FALSE
TRUE
-
Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
nOut_a
nHighLimit
wTir
wTir
0
nLowLimit
bUp
TRUE
FALSE
bDown
TRUE
FALSE
bDown
bInact
Function
FALSE
FALSE
The nOut_a output signal remains unchanged.
FALSE
The nOut_a output signal runs to its upper limit value (nHighLimit).
TRUE
The nOut_a output signal runs to its lower limit value (nLowLimit).
TRUE
The nOut_a output signal remains unchanged.
-
TRUE
The motor potentiometer function is deactivated. The nOut_a
output signal responds according to the function selected via
Function.