Basic Settings; Optimising The Control Mode - Lenze 8400 StateLine C Reference Manual

L-force drives; e84avsc series;
Hide thumbs Also See for 8400 StateLine C:
Table of Contents

Advertisement

8400 StateLine C | Reference manual
Motor control (MCTRL)
V/f characteristic control - energy-saving (VFCplusEco)
5.5.3

Basic settings

The "Initial commissioning steps" listed in the table below are sufficient for the V/f
characteristic control - energy-saving (VFCplusECo).
 Detailed information on the individual steps can be found in the following
subchapters.
Initial commissioning steps
1. Determine the motor control:
C00006
2. The required motor data are pre-initialised depending on the device and thus, they do not need to be
entered directly.In order to achieve a high energy optimisation, these motor data can be entered (see the
following section).
Set the motor selection/motor data
• When selecting and parameterising the motor, the motor nameplate data and the equivalent circuit
diagram data are relevant. Detailed information can be found in the
chapter.
Depending on the motor manufacturer, proceed as follows:
Lenze motor:
Selecting a motor from the motor catalogue in the
»Engineer«
- or -
1. Set the motor nameplate data
2.
Automatic motor data identification
3.
Defining current limits (Imax
Tip!
Information on the optimisation of the control mode and the adaptation to the
real application is provided in the chapter
Parameterisable additional functions are described correspondingly in the chapter
"Parameterisable additional
148
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
= "11: VFCplusEco: V/f energy-saving"
( 107)
controller).
functions".
L
"Motor selection/Motor
Third party manufacturer's motor:
1. Set the motor nameplate data
2.
Automatic motor data identification
equivalent circuit diagram manually:
C00084: Motor stator resistance
C00085: Motor stator leakage inductance
C00092: Motor magnetising inductance
( 130)
"Optimising the control
( 193)
Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011
data"
or set known
mode".
( 149)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents