Setting The Baud Rate - Lenze 8400 StateLine C Reference Manual

L-force drives; e84avsc series;
Hide thumbs Also See for 8400 StateLine C:
Table of Contents

Advertisement

8400 StateLine C | Reference manual
System bus "CAN on board"
Possible settings via DIP switch
10.2.2

Setting the baud rate

The baud rate can be set via code
Note!
• All DIP switches (a ... d, 1 ... 64) = OFF (Lenze setting):
– At switching on, the settings under code
• Preset baud rate: 500 kbps
DIP switch position
d
OFF
OFF
OFF
OFF
OFF
OFF
10.2.3
Setting the node address
The node address can be set via code
 The labelling on the housing corresponds to the values of the individual DIP switches
for determining the node address.
 The valid address range depends on the number of SDO channels set in C00366:
– 1 SDO (Lenze setting): 1 ... 127
– 2 SDO: 1 ... 63
Note!
• The addresses of the nodes must differ from each other.
• All DIP switches (a ... d, 1 ... 64) = OFF (Lenze setting):
– At switching on, the settings under code
432
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
C00351
C00351
(baud rate) will become active.
c
b
A
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
C00351
(baud rate) will become active.
L
or with the DIP switches a to d.
C00350
Baud rate
20 kbps
50 kbps
125 kbps
250 kbps
500 kbps
1000 kbps*
C00350
or with the DIP switches 1 to 64.
C00350
Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011
(node address) and
* From version 11.00.00
(node address) and