WSM KX080-3 Service

(5) Check performance of air conditioning system

1) Calculate the relative humidity from the psychrometric graph by comparing the wet- and dry-bulb
readings of the psychrometer at the air inlet.
HOW TO READ THE GRAPH:
After measuring the temperatures of wet- and
dry-bulb thermometers at the evaporator air
inlet, relative humidity (%) can be obtained.
Example: Supposing dry- and wet- bulb tem-
peratures at the evaporator air inlet are 25°C
(77°F) and 19.5°C (67°F) respectively. The
point of intersection of the dotted lines in the
graph is 60%.
Fig. Psychrometric Graph
2) Measure the dry-bulb temperature at the cool
air outlet, and calculate the difference
between the inlet dry-bulb and outlet dry-
bulb temperatures.
In this case ;
inlet dry-bulb = 25°C
outlet dry-bulb = 8°C
Then, temp. difference = 17°C
3) Check that the intersection of the relative
humidity and temperature difference is
above the line.
If the intersection is within a line A and a line
B, cooling performance is satisfactory.
Fig. Relative Humidity Graph
VI-S-22
VI Air Conditioner