Processing details
• These instructions convert the 16-bit unsigned binary data in the device specified by (s) to a single-precision real number,
and store the real number in the device specified by (d).
SM402
M0
Operation error
There is no operation error.
7 APPLICATION INSTRUCTIONS
744
7.9 Real Number Instructions
MOVP
K1234
D0
(s)
(d)
UINT2FLT
D0
D100
(s)
b15
∙∙∙
b0
D0
04D2H
D101, D100
(1234)
(d)
b31
∙∙∙
b16
b15
∙∙∙
b0
449AH
4000H
(1234.0)