Analog Input Signals; Sub-Function Parameters - ABB REQ650 Applications Manual

Breaker protection, relion 650 series
Hide thumbs Also See for REQ650:
Table of Contents

Advertisement

Section 11
Monitoring
11.6.3.3
11.6.3.4
238

Analog input signals

Up to 40 analog signals can be selected among internal analog and analog input
signals. PCM600 is used to configure the signals.
The analog trigger of Disturbance report is not affected if analog input M is to be
included in the disturbance recording or not (OperationM = On/Off).
If OperationM = Off, no waveform (samples) will be recorded and reported in
graph. However, Trip value, pre-fault and fault value will be recorded and reported.
The input channel can still be used to trig the disturbance recorder.
If OperationM = On, waveform (samples) will also be recorded and reported in
graph.
NomValueM: Nominal value for input M.
OverTrigOpM, UnderTrigOpM: Over or Under trig operation, Disturbance report
may trig for high/low level of analog input M (On) or not (Off).
OverTrigLeM, UnderTrigLeM: Over or under trig level, Trig high/low level relative
nominal value for analog input M in percent of nominal value.

Sub-function parameters

All functions are in operation as long as Disturbance report is in operation.
Indications
IndicationMaN: Indication mask for binary input N. If set (Show), a status change
of that particular input, will be fetched and shown in the disturbance summary on
local HMI. If not set (Hide), status change will not be indicated.
SetLEDN: Set red LED on local HMI in front of the IED if binary input N changes
status.
Disturbance recorder
OperationM: Analog channel M is to be recorded by the disturbance recorder (On)
or not (Off).
If OperationM = Off, no waveform (samples) will be recorded and reported in
graph. However, Trip value, pre-fault and fault value will be recorded and reported.
The input channel can still be used to trig the disturbance recorder.
If OperationM = On, waveform (samples) will also be recorded and reported in
graph.
Setting information
SetInfoInDrep: Parameter used to enable or disable the settings information in
disturbance header.
1MRK 505 383-UEN A
M12179-92 v5
M12179-389 v3
M12179-448 v4
M12179-446 v4
GUID-B0D40F6D-3CE4-4FF3-81B4-B453FDD389CB v1
Breaker protection REQ650 2.2 IEC
Application manual