Signals; Technical Data; Controllable Gate Function Block Gate; Function Block - ABB REL650 Technical Manual

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 382-UEN A
13.7.1.2
13.7.1.3
13.7.2
13.7.2.1
13.7.2.2
Line distance protection REL650 2.2 IEC
Technical manual

Signals

Table 298:
AND Input signals
Name
Type
INPUT1
BOOLEAN
INPUT2
BOOLEAN
INPUT3
BOOLEAN
INPUT4
BOOLEAN
Table 299:
AND Output signals
Name
Type
OUT
BOOLEAN
NOUT
BOOLEAN

Technical data

Table 300:
Number of AND instances
Logic block
3 ms
AND
60

Controllable gate function block GATE

The Controllable gate function block (GATE) is used for controlling if a signal
should be able to pass from the input to the output or not depending on a setting.

Function block

GATE
INPUT
OUT
IEC04000410-2-en.vsd
IEC04000410 V2 EN-US
Figure 255:
GATE function block
Signals
Table 301:
GATE Input signals
Name
Type
INPUT
BOOLEAN
Default
Description
1
Input signal 1
1
Input signal 2
1
Input signal 3
1
Input signal 4
Description
Output signal
Inverted output signal
Quantity with cycle time
8 ms
60
Default
Description
0
Input to gate
Section 13
Logic
PID-3437-INPUTSIGNALS v7
PID-3437-OUTPUTSIGNALS v7
GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v2
100 ms
160
IP11021-1 v2
M11489-3 v2
M11490-3 v2
PID-3801-INPUTSIGNALS v6
493

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series

Table of Contents