Controllable Gate Function Block Gate - ABB Relion Technical Manual

Generator protection
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

1MRK 502 048-UUS A
Table 306:
PULSETIMER Non group settings (basic)
Name
Values (Range)
t
0.000 - 90000.000
13.3.1.5
Technical manual
Table 305:
PULSETIMER Output signals
Name
Type
OUT
BOOLEAN
Settings
Unit
Step
s
0.001

Controllable gate function block GATE

Identification
Function description
Controllable gate function block
Functionality
The GATE function block is used for controlling if a signal should pass from the input to
the output or not, depending on setting.
Function block
GATE
INPUT
OUT
IEC09000295-1-en.vsd
IEC09000295 V1 EN
Figure 220:
GATE function block
Signals
Table 307:
GATE Input signals
Name
Type
INPUT
BOOLEAN
Table 308:
GATE Output signals
Name
Type
OUT
BOOLEAN
Description
Output signal
Default
Description
0.010
Pulse time length
IEC 61850
IEC 60617
identification
identification
GATE
Default
Description
0
Input signal
Description
Output signal
Section 13
Logic
ANSI/IEEE C37.2
device number
-
-
479