Figure 4-2 Belt Failure Detection - Siemens MICROMASTER 430 Manual

Hide thumbs Also See for MICROMASTER 430:
Table of Contents

Advertisement

4.5.2
Function
MICROMASTER 430
6SE6400-5AC00-0BP0
www.eltra-trade.com
Belt Failure Detection
Recognizes mechanical faults in drive section e.g. torn V-belt, pumps which have
run dry etc.
Torque[Nm]
P2189
Upper torque threshold 3
P2190
Lower torque threshold 3
P2187
Upper torque threshold 2
P2188
Lower torque threshold 2
P2185
Upper torque threshold 1
P2186
Lower torque threshold 1
Threshold frequency 1
Figure 4-2
Belt Failure Detection
A torque band is monitored. This enables underload and overload conditions to be
recognized (e.g. ventilator not running correctly)
Comparison between current speed / torque curve with programmed envelope
curve. The upper and lower frequency curve can be specified via three supporting
points each. In addition a dead time until the function is triggered can be defined.
This avoids accidental triggering due to transient events.
For additional settings please refer to parameter list P2181 and following.
Operating Instructions
4 MICROMASTER 430 functions
P2183
P2182
Threshold frequency 2
P1082
Max. frequency
Frequency
[Hz]
P2184
Threshold frequency 3
53